200 Tons at ARI Conditions at 120° F Ambient Temp.
Operating temperature Range 0F to 120F
Coldest Temperature Leaving 5° F
Flow Rate: 480 Gallons/ Minute at 100 Feet of Head
Max flow rate 1000 gpm& Min flow rate 78 gpm
460 Volts
MCA Minimum Circuit Ampacity 500 Amps
MOP is 600 Amps
300 Tons at ARI Conditions at 95° F Ambient Temp.
Operating temperature Range 5F to 100F
Coldest Temp. Leaving 5° F
Flow Rate: 720 Gallons/ Minute at 100 Feet of Head
Max flow rate 2100 gpm & Min flow rate 60 gpm
460 Volts
MCA Minimum Circuit Ampacity 800 Amps
MOP is 1000 Amps
100 Tons at ARI Conditions at 120° F Ambient Temp
Operating temperature Range 0° F to 120° F
Coldest Temperature Leaving 5° F
Flow Rate: 240 Gallons/ Minute at 120 Feet of Head
Max flow rate 360 gpm & Min flow rate 78 gpm
Dual voltage
MCA 230 Volts =415 amps 460 Volts=210 amps
MOP is 500 Amps @ 230 volts. MOP is 250 amps @ 460 volts
310 Tons at ARI Conditions at 95° F Ambient Temp.
Operating temperature Range 5° F to 125° F
Coldest Temp. Leaving 5° F
Flow Rate: 720 Gallons/ Minute at 100 Feet of Head
Max flow rate 2100 gpm & Min flow rate 60 gpm
460 Volts
MCA Minimum Circuit Ampacity 650 Amps
MOP is 1000 Amps
200 Tons at ARI Conditions at 120° F Ambient Temp.
Operating temperature Range 0° F to 120° F
Coldest Temperature Leaving 5° F
Flow Rate: 480 Gallons/ Minute at 100 Feet of Head
Max flow rate 1000 gpm & Min flow rate 78 gpm
460 Volts
MCA Minimum Circuit Ampacity 500 Amps
MOP is 600 Amps
Chiller Rides on air ride Trailer with on board Work Lights & 120 Volt Outlets
Integral Pre-Piped & Wired Chilled Water Pump and starter
Right Angle Suction Diffuser/Strainer
Cross Connected Gauges on Pump & Evaporator
BTU/TON Meter
6" Flange Piping Connections with Lug Isolation Valves
On Board skid with Air Separator, Vent Relief Valve & Bladder Type Expansion Tank